Part Number Hot Search : 
M1602 051AS2 C3SMB TC143E 0001TR 1001D1 ACTZTB PDB50N12
Product Description
Full Text Search
 

To Download DRA18-05 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 DRA18 SERIES
AC - DC DIN RAIL MOUNTABLE 18W CLASS 2 POWER SUPPLY INDUSTRIAL CONTROL EQUIPMENT
FEATURES
UL / cUL / TUV / CE UNIVERSAL INPUT 90~265VAC HIGH EFFICIENCY UP TO 77% SHORT CIRCUIT PROTECTION INTERNAL INPUT FILTER 2 YEARS WARRANTY
MODEL LIST
MODEL NO. INPUT VOLTAGE
90~265 VAC 90~265 VAC 90~265 VAC 90~265 VAC
OUTPUT OUTPUT WATTAGE VOLTAGE Single Output Models
15 WATTS 18 WATTS 18 WATTS 18 WATTS + 5 VDC + 12 VDC + 15 VDC + 24 VDC
OUTPUT CURRENT
3000 mA 1500 mA 1200 mA 750 mA
EFF. (typ.)
75% 77% 77% 77%
EFF. (min.)
73% 75% 75% 75%
DRA18-05 DRA18-12 DRA18-15 DRA18-24
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
GENERAL
Characteristics
Switching frequency Isolation voltage Isolation resistance Ambient temperature Derating Storage temperature M.T.B.F. Relative humidity Dimension Cooling Case material
Conditions
Vi nom, Io nom Input / Output Input / Output, @ 500VDC Operating at Vi nom, Io 70% ...100% Vi nom, Io nom +51 to +71 C Non operational According to MIL-HDBK-217F, GF40 Vi nom, Io nom L90 x W22.5 x D115 Free air convection Plastic
o
min.
100 3,000 100 -10 -25
typ.
max.
unit
KHz VAC M
+ 50 2 + 85 195,000 95
o o
C C
%/ C
o
Hrs % RH mm
20
INPUT SPECIFICATIONS
Characteristics
Rated input voltage Input voltage range Line frequency Inrush current Io nom Ta min ... Ta max, Io nom Vi nom, Io nom Io nom Vi : 115VAC Vi : 230VAC AC in DC in
Conditions
min.
100 90 120 47
typ.
max.
240 265 370 63 10 18
unit
VAC VAC VDC Hz A A
DB LECTRO Inc. 3600 boul. Matte suite i Brossard Qc J4Y-2Z2 tel:(450)-444-1424 fax:(450)-444-4714 www.dblectro.com
DRA18 SERIES
IND. CONT. EQ.
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed
o
OUTPUT SPECIFICATIONS
Characteristics
Output voltage accuracy Minimum load Line regulation Load regulation Transient recovery time Temperature coefficient Ripple & noise Hold up time Voltage trim range DC ON indicator threshold at start up Vi nom Io nom, Vi min ...Vi max Vi nom, Io min ...Io nom 50% load step changed Vi nom, Io min Vi nom, Io nom,BW = 20MHz Io nom Vi nom, Io nom Vi nom, Io nom Vi = 115VAC Vi = 230VAC 5V ...15V models 24V model 5V model 12V model 15V model 24V model DC LOW indicator threshold after start up Vi nom, Io nom 5V model 12V model 15V model 24V model Efficiency Vi nom, Io nom, Po / Pi 20 75 - 10 - 10 4.5 10.8 13.5 21.6 3.75 9 11.25 18 Up to 77%, See model list 4.5 10.8 13.5 21.6 + 15 + 20 300 0.02 50
o
Conditions
Vi nom, Io min ...Io nom
min.
0
typ.
max.
1 1 2
unit
% % % % S %/C mV ms ms % % VDC VDC VDC VDC VDC VDC VDC VDC
CONTROL AND PROTECTION
Characteristics
Input fuse Rated over load protection Over voltage protection Output short circuit Vi nom Vi nom, Io nom Vi nom, Io nom 110 125 Hiccup mode
Conditions
min.
typ.
max.
135 145
unit
% %
T2A / 250VAC internal
APPROVALS AND STANDARDS
UL / cUL TUV CE FCC UL508 / UL1310 Listed, Class 2 Power Supply EN60950 EN50081-1 / EN55022 for EMI EN50082-1 / EN55024 for EMS Class B
CIRCUIT SCHEMATIC
Block diagram for DRA18 series
L Fuse
Inrush Current Switching Limiter and Device Rectifier
Vo +
Rectifier
Line Filter
N Y
Current Detection
Vo -
Control
Opto Isolation Opto Isolation
Reference & Error Amp. Over Voltage Detection Output Level Detection
Vout ADJ.
DC ON (Green LED) DC LOW (Red LED)
DB LECTRO Inc. 3600 boul. Matte suite i Brossard Qc J4Y-2Z2 tel:(450)-444-1424 fax:(450)-444-4714 www.dblectro.com
DRA18 SERIES
IND. CONT. EQ.
MECHANISM & PIN CONFIGURATION
mm [inch]
22.5[0.89] 115 [4.53]
CONSTRUCTION
Easy snap-on mounting onto the DIN-Rail (TS35/7.5 or TS35/15), unit sits safely and firmly on the rail; no tools required even to remove
21
V- V+
DC Output LO ON
INSTALLATION
Ventilation / Cooling Normal convection Above/below 25m/m free space For cooling recommended Connector size range Solid:0.2-2.0mm2(AWG24-14) (use copper conductors only)
90.0 [3.60]
Vout ADJ.
NL
345
PHYSICAL CHARACTERISTICS
CASE SIZE CASE MATERIAL WEIGHT 90 x 22.5 x 115 mm 3.6 x 0.89 x 4.53 inches Plastic 150 g
PIN ASSIGNMENT
PIN NO.
OUT
1 2 3 4 5
Designation
V+ VN L ON LO Vout ADJ.
Description
Positive output terminal Negative output terminal Ground this terminal to minimize high-frequency emissions Input terminals (neutral conductor, no polarity at DC input) Input terminals (phase conductor, no polarity at DC input) Operation indicator LED DC LOW indicator LED Trimmer-potentiometer for Vout adjustment
DERATING
100 Power out [ % ]
60
0 -20
o
OTHER
IN
50 Temperature [ C ]
71
DB LECTRO Inc. 3600 boul. Matte suite i Brossard Qc J4Y-2Z2 tel:(450)-444-1424 fax:(450)-444-4714 www.dblectro.com


▲Up To Search▲   

 
Price & Availability of DRA18-05

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X